Air Duct Size Calculator

Air Distribution Engineering

Comprehensive technical specifications for optimal duct system design.

  • Velocity Parameters
    • Main Trunk: 800-1000 FPM
    • Branch Ducts: 600-800 FPM
    • Residential Supply: 700-900 FPM
    • Return Air: 600-700 FPM
  • Friction Rate Design
    • Optimal Range: 0.08-0.15 iwc/100ft
    • Maximum Rate: 0.25 iwc/100ft
    • Branch Loss: 0.05-0.08 iwc
    • Total Static: 0.5-1.0 iwc
  • Sizing Equations
    • Area = CFM ÷ Velocity
    • Diameter = √(4 × Area ÷ π)
    • Aspect Ratio: ≤ 4:1 recommended
    • Equivalent Length: L + (1.5 × D)

System Design Parameters

Critical specifications for duct system performance:

  • Flow Characteristics
    • Reynolds Number: 4000+ turbulent
    • Roughness Factor: ε = 0.0003 ft
    • Dynamic Losses: Σ(C × Vp)
    • Leakage Class: ≤ 6 (sealed)
  • Material Properties
    • Sheet Metal Gauge: 24-30 GA
    • Insulation R-Value: 6-8 min
    • Vapor Barrier: 0.02 perm max
    • Fire Rating: Class 1/Class A
  • Installation Standards
    • Hanger Spacing: 8-10 ft max
    • Sealing Level: SMACNA Class A
    • Support Load: 1.5 × weight
    • Deflection Limit: L/240 max

Performance Metrics

Key parameters for system evaluation and testing:

  • Testing Standards
    • Pressure Test: 2× operating
    • Leakage Rate: ≤ 5% design flow
    • Balance Tolerance: ±10% design
    • Noise Criteria: NC-35 max
  • System Efficiency
    • Transport Factor: 0.75-0.85
    • Fan Power Index: ≤ 0.8 W/cfm
    • Distribution Loss: ≤ 15%
    • System Effect Factor: ≤ 0.5
  • Acoustic Control
    • Breakout Loss: 40+ dB
    • Insertion Loss: 20-30 dB
    • Regenerated Noise: NC-25
    • Room Criteria: RC-30 max